Michigan HVAC Practice Questions
These 42 worked questions are published free as part of PassProfessor’s Michigan HVAC Exam Prep, for the mechanical contractor license’s HVAC Equipment classification examination (MCL 339.5807(2)(b)), administered by PSI for the Bureau of Construction Codes. Each question is a bank item, printed with its key, a full explanation, and its cited reference.
Cap statement: this examination presents 150 questions in one sitting, so the worked-question limit for this program is 45. This page publishes 42, and 3 more fully audited questions are held in reserve — 42 published plus 3 reserve equals the 45 maximum. The free 20-question sample is separate and does not count toward this limit.
PSI publishes no weighted outline for this examination — only a narrative scope. The 42 questions below are spread across that published scope (heating and cooling principles and theories; installation of HVAC equipment and systems; ductwork; gas piping; venting; codes and standards; and the law layer every sitting carries, from the Skilled Trades Regulation Act, 2016 PA 407 and the Stille-DeRossett-Hale Single State Construction Code Act, 1972 PA 230), using the bank’s topic pools. The spread follows the published scope, not weights, and no distribution chart is installed.
Three facts to carry into every question below. First, the passing standard is PSI’s published “Minimum Passing Score 75%” — not the 70% figure older sources print from a superseded rule. Second, the sitting is open book but clean book: bound references only, with no highlighting, marking, or tabs, so these worked questions train the fluency the room actually requires. Third, the money sits in two separate layers that are never combined: a $100 examination fee paid to PSI, and a separate $100 per-year license fee paid to the Department.
A. Heating & cooling principles and theories
Question 1 — Heating Systems
A modern residential gas furnace uses a hot-surface igniter. What material and behavior most accurately describe this igniter?
- A spark electrode that clicks continuously throughout the heating cycle to re-light the burners whenever the thermostat calls for heat
- A silicon carbide or silicon nitride element that glows hot enough to ignite gas directly
- A standing pilot that stays lit all season and lights the main burners
- A thermocouple that generates voltage to open the gas valve
Correct: B — A silicon carbide or silicon nitride element that glows hot enough to ignite gas directly
The hot-surface igniter is a resistive silicon carbide or nitride element that glows to well above gas ignition temperature and lights the burners directly, which is option B. A spark electrode (A) describes direct-spark ignition, not hot-surface ignition, a standing pilot (C) describes older pilot systems, and a thermocouple (D) is a pilot safety sensor, not an igniter.
Reference: Modern Refrigeration and Air Conditioning; Gas furnace manufacturer installation and service literature
Question 2 — Heating Systems
A furnace lights reliably but shuts down a few seconds after ignition on every call for heat. The flame sensor rod is visibly coated and the measured flame current is well below the manufacturer's minimum. What is the most appropriate first repair?
- Replace the gas valve because manifold pressure must be low
- Replace the hot-surface igniter because it is staying on too long
- Remove and clean the flame sensor rod and recheck flame current
- Replace the inducer motor because draft is tripping the burners
Correct: C — Remove and clean the flame sensor rod and recheck flame current
A coated flame rod cannot pass adequate DC flame current, so the board stops recognizing flame and closes the gas valve for safety; cleaning the rod and rechecking current, option C, addresses the cause. Low manifold pressure (A) would more likely cause weak ignition rather than this consistent post-ignition dropout, the igniter (B) has already proven it can light the gas, and an inducer fault (D) would typically prevent ignition in the first place.
Reference: Modern Refrigeration and Air Conditioning
Question 3 — Heating Systems
A furnace starts its inducer on a call for heat, but the igniter never glows and the burners never light. The pressure switch contacts remain open, the vent is clear, and the inducer produces adequate vacuum. What does this pattern most strongly indicate?
- The pressure switch has failed and should be replaced after verifying adequate draft
- The flame sensor is dirty and coated with oxide, so it is preventing the igniter from ever being energized
- The gas valve is stuck open and flooding the heat exchanger
- The high-limit switch is open because of low airflow
Correct: A — The pressure switch has failed and should be replaced after verifying adequate draft
The pressure switch proves draft before ignition is allowed, so adequate vacuum with contacts that stay open points to a failed switch, option A, once draft and tubing are verified. A dirty flame sensor (B) causes shutdown after light-off, not failure to start ignition, a stuck-open gas valve (C) would not hold off the igniter, and an open limit (D) does not explain the pressure-switch behavior.
Reference: Modern Refrigeration and Air Conditioning; Gas furnace manufacturer installation and service literature
Question 4 — Heating Systems
What does a furnace's AFUE rating represent?
- Its maximum hourly gas input in a standardized laboratory test with the burners firing continuously at full rate
- Its electrical efficiency at full blower speed
- The ratio of annual gas input to annual gas cost
- The share of fuel energy converted to useful heat over a typical heating season
Correct: D — The share of fuel energy converted to useful heat over a typical heating season
AFUE is annual fuel utilization efficiency – useful heat delivered over a season divided by fuel energy consumed – which is option D. It is not a peak input figure (A), not an electrical rating (B), and while it affects operating cost it is not itself a ratio involving dollars (C).
Reference: Modern Refrigeration and Air Conditioning; DOE residential furnace efficiency guidance
Question 5 — Heating Systems
A 96% AFUE furnace is installed in a basement. Its flue gases are relatively cool and the vent system is designed to operate under positive pressure with a condensate drain at the furnace. How should its venting be handled?
- Vent it into an existing unlined masonry chimney with no corrosion-resistant liner, relying on the chimney's natural draft to carry the cool flue gases out
- Use a single-wall metal connector into a Type B vent shared with a water heater
- Vent it with the manufacturer-approved sealed plastic vent system and drain the condensate as directed
- Let it vent into the basement and rely on dilution air to carry products out
Correct: C — Vent it with the manufacturer-approved sealed plastic vent system and drain the condensate as directed
A 96% unit is a condensing, positive-pressure (Category IV) appliance, so it needs the manufacturer-approved sealed vent material and condensate handling in option C. Cool, moisture-laden flue gas would condense in and damage an unlined masonry chimney (A), Type B/common venting (B) is for negative-pressure non-condensing appliances and risks spillage, and venting into the space (D) is a carbon-monoxide hazard.
Reference: IFGC fuel-gas piping provisions; IMC mechanical venting provisions; Gas furnace manufacturer installation and service literature
Question 6 — Heating Systems
A furnace delivers 80,000 Btuh of heat output while moving 1,200 cfm of air. Using rise = output / (1.08 x cfm), what is the approximate air temperature rise across the furnace?
- About 42 degrees F
- About 62 degrees F
- About 77 degrees F
- About 93 degrees F
Correct: B — About 62 degrees F
80,000 / (1.08 x 1,200) = 80,000 / 1,296, or about 62 degrees F, which is option B. Option A understates the result as if output were far lower, option C is what results from mistakenly using a 100,000 Btuh input instead of output, and option D would require substantially less airflow than the stated 1,200 cfm.
Reference: Modern Refrigeration and Air Conditioning
Question 7 — Refrigeration Principles & Components
In a standard vapor-compression system, in what order does refrigerant pass through the four major components, starting at the compressor outlet?
- Compressor to condenser to metering device to evaporator, then back to the compressor
- Compressor to metering device to condenser to evaporator, then back to the compressor
- Compressor to evaporator to condenser to metering device, then back to the compressor
- Compressor to condenser to evaporator to metering device, then back to the compressor
Correct: A — Compressor to condenser to metering device to evaporator, then back to the compressor
Refrigerant leaves the compressor as high-pressure vapor, rejects heat and condenses, is throttled at the metering device, then absorbs heat in the evaporator before returning to the compressor. Option B throttles hot discharge gas before it can condense, option C puts the evaporator before the condenser, and option D places the metering device after the evaporator, so none of those can sustain the cycle.
Reference: Modern Refrigeration and Air Conditioning
Question 8 — Refrigeration Principles & Components
What is the primary function of the compressor in a refrigeration system?
- To reject heat from the refrigerant to the outdoor air as it flows through the condenser coil, fins, and fan assembly on a hot summer day
- To raise the pressure and temperature of low-pressure superheated vapor so heat can be rejected at the condenser
- To lower refrigerant pressure and create the cooling effect directly
- To separate liquid refrigerant from vapor before the evaporator
Correct: B — To raise the pressure and temperature of low-pressure superheated vapor so heat can be rejected at the condenser
The compressor draws in low-pressure superheated vapor and compresses it, raising its pressure and temperature so the condenser can reject heat. Option A describes the condenser, option C describes the metering device, and option D describes a separator or accumulator, not compression.
Reference: Modern Refrigeration and Air Conditioning
Question 9 — Refrigeration Principles & Components
A technician watches an air-cooled condenser on a hot day. The first passes of the coil are cooling hot discharge gas, the middle passes are changing state at a nearly constant temperature, and the last passes cool the liquid a few degrees further. What are those three processes, in order?
- Subcooling, desuperheating, then condensing
- Evaporating, condensing, then desuperheating
- Desuperheating, condensing, then subcooling
- Condensing, evaporating, then subcooling
Correct: C — Desuperheating, condensing, then subcooling
Discharge vapor first loses sensible heat in desuperheating, then condenses at its saturation temperature, then the liquid is subcooled below saturation. Option A reverses the first two steps, option B wrongly includes evaporation, which occurs in the evaporator, and option D starts with condensing even though superheated gas must be desuperheated first.
Reference: Modern Refrigeration and Air Conditioning
Question 10 — Cooling Systems: Service, Diagnostics & Repair
A split air conditioner shows low suction pressure, a frost line forming at the evaporator outlet, low evaporator superheat, and a supply-to-return temperature split of 27°F. Airflow checks have not yet been done. What is the most likely cause?
- An overcharge of refrigerant flooding the evaporator, with liquid stacking in the receiver and condenser
- A dirty condenser coil raising the head pressure
- Low indoor airflow across an under-loaded, excessively cold evaporator coil
- Noncondensable gas trapped in the condenser
Correct: C — Low indoor airflow across an under-loaded, excessively cold evaporator coil
Low airflow unloads the evaporator, dropping suction pressure and superheat while the reduced air volume picks up an abnormally large temperature split and the coil runs cold enough to frost. Option A would tend to raise suction pressure rather than lower it, and option B primarily raises head pressure instead of frosting the evaporator. Option D also drives head pressure up and does not explain the high temperature split.
Reference: Refrigeration and Air Conditioning Technology; manufacturer-agnostic industry practice
Question 11 — Cooling Systems: Service, Diagnostics & Repair
What does a thermostatic expansion valve (TXV) control under normal operating conditions?
- Evaporator superheat, by modulating refrigerant flow in response to suction-line temperature and evaporator pressure
- Condenser subcooling, by holding a fixed liquid level in the receiver
- Compressor discharge temperature, by bypassing hot gas around the condenser, using a strap-on sensor clamped to the discharge line
- Indoor airflow, by signaling the blower to change speed with load
Correct: A — Evaporator superheat, by modulating refrigerant flow in response to suction-line temperature and evaporator pressure
A TXV senses suction-line temperature against evaporator pressure and modulates flow to hold its superheat setting as load changes. Option B is wrong because subcooling is a result of condenser and charge conditions, not the valve's controlled variable on a typical system. Option C describes a hot-gas bypass arrangement, and option D confuses a refrigerant metering device with an air-side control.
Reference: Modern Refrigeration and Air Conditioning; manufacturer-agnostic industry practice
Question 12 — Cooling Systems: Service, Diagnostics & Repair
A TXV system in cooling mode has normal evaporator superheat, both pressures somewhat high, and subcooling of 24°F against a manufacturer target of 10°F. Cooling capacity is slightly reduced. What condition best fits these readings?
- Overcharge, with excess liquid backing up in the condenser
- Undercharge, with the condenser only partly filled with liquid
- A restricted liquid-line filter drier starving the TXV
- Low indoor airflow across the evaporator coil
Correct: A — Overcharge, with excess liquid backing up in the condenser
With a TXV holding superheat steady, excess charge collects in the condenser and shows up as abnormally high subcooling with elevated pressures. Option B is the opposite condition and would produce low subcooling, while option C starves the valve and raises superheat rather than holding it normal. Option D lowers suction pressure and superheat, which does not match the normal superheat reading here.
Reference: Refrigeration and Air Conditioning Technology; manufacturer-agnostic industry practice
Question 13 — Load Calculation & System Design
Which set lists major heating load components in a Manual J calculation?
- Only window glass area
- Only duct color and filter type
- Transmission through envelope, infiltration, and duct losses
- Refrigerant type and line-set length only, with no envelope or infiltration terms
Correct: C — Transmission through envelope, infiltration, and duct losses
Heating load is driven mainly by heat transmission through walls, ceilings, floors and glass, plus infiltration and duct losses, so C is correct. A and D each name only one minor or unrelated factor, and B names items that do not drive the load.
Reference: ACCA Manual J
B. Installation of HVAC equipment and systems
Question 14 — Equipment Installation & Commissioning
When placing an outdoor condensing unit, which placement practice best supports reliable operation and service access?
- Set it level on a stable pad, keep the coil clear of obstructions and discharge-air recirculation, and leave the clearances the maker specifies for airflow and service
- Tilt it toward the house so condensate and rain run toward the building
- Push it tight against two walls to shield it from wind on all sides
- Set it directly on bare soil so the pad cannot crack in freezing weather
Correct: A — Set it level on a stable pad, keep the coil clear of obstructions and discharge-air recirculation, and leave the clearances the maker specifies for airflow and service
A level unit on a stable pad with specified clearances gets full airflow, avoids recirculating hot discharge air, and can be serviced safely. Option B risks water at the building and an unlevel compressor, option C starves the coil and blocks service, and option D allows settling and tilting as soil shifts.
Reference: Manufacturer service and installation literature; Modern Refrigeration and Air Conditioning
Question 15 — Equipment Installation & Commissioning
A line set must rise 18 feet from an indoor coil downstairs to an outdoor unit above it, and the maker requires oil management on the riser. What should the installer do?
- Oversize the suction riser well above the listed size so velocity rises
- Slope the liquid line uphill so oil drains back to the indoor coil, and rely on gravity in that liquid line to return oil that has logged in the vertical riser during low-load operation
- Size the riser as listed and install a properly formed trap at the base of the vertical riser where the maker requires one
- Add extra oil to the compressor to replace whatever stays in the riser
Correct: C — Size the riser as listed and install a properly formed trap at the base of the vertical riser where the maker requires one
A correctly sized riser keeps vapor velocity high enough to carry oil, and a trap at the base helps oil lift in stages instead of logging in the riser. Option A is backwards because oversizing lowers velocity, option B confuses the liquid line with oil return in the suction riser, and option D overfills the crankcase without fixing oil logging.
Reference: Manufacturer service and installation literature; Modern Refrigeration and Air Conditioning
Question 16 — Packaged & Manufactured Systems
A rooftop unit in cooling mode has suitable outdoor air for free cooling, yet the economizer dampers stay at minimum position and the compressor runs continuously. Mixed-air temperature tracks return air closely. What should be checked first?
- Replace the compressor contactor, because continuous compressor operation proves the contactor is welded and is also holding the dampers closed
- Verify power and signal at the damper actuator and inspect the mixed-air and outdoor-air sensors that tell the economizer when to open
- Add refrigerant charge, because low charge forces the control board to lock out economizer operation until pressures recover fully
- Close the manual fresh-air intake on the roof, because excess outdoor air at the hood prevents the actuator from moving the blades
Correct: B — Verify power and signal at the damper actuator and inspect the mixed-air and outdoor-air sensors that tell the economizer when to open
The economizer can only open when its actuator has power and signal and its sensors correctly report favorable outdoor air, so actuator and sensor checks come first. A welded contactor would not hold dampers closed, low charge does not lock out an economizer in this way, and closing the intake treats ventilation as the fault rather than testing the controls.
Reference: Manufacturer packaged-unit service guidance; ASHRAE ventilation and economizer practice; International Mechanical Code general practice
Question 17 — Hydronics & Boilers
A water chiller produces 44°F leaving chilled water while the evaporator saturated refrigerant temperature is 38°F. What is the evaporator approach, and what does it describe?
- 6°F — the difference between leaving chilled-water temperature and evaporating refrigerant temperature
- 82°F — the sum of the leaving water and refrigerant temperatures added together
- 38°F — the refrigerant temperature alone, regardless of the water temperature measured at the outlet
- 44°F — the leaving water temperature alone, regardless of what the refrigerant is doing inside the evaporator
Correct: A — 6°F — the difference between leaving chilled-water temperature and evaporating refrigerant temperature
The approach is 44 minus 38, or 6°F, and a widening approach at the same load points to poor heat transfer. Option B adds the temperatures, which has no diagnostic meaning, option C names only the refrigerant temperature, and option D names only the water temperature, so neither describes a difference between the two.
Reference: ASHRAE Handbook – HVAC Systems and Equipment; Manufacturer service and installation literature
Question 18 — Commercial Refrigeration Systems
A walk-in cooler holds product temperature except after busy delivery periods, when box temperature rises for hours. The coil, fans, and refrigerant readings check normal, but a door sweep is torn and the gasket pulls away at one corner. What is the most likely explanation?
- Warm, moist outside air infiltrating through the door leaks, adding latent and sensible load and frosting the coil
- A failed evaporator pressure regulator that is holding suction pressure too high at all hours, including overnight periods when the doors remain closed and no warm product is loaded
- An oversized compressor that short-cycles too often to dehumidify the box
- A liquid-line sight glass that has become too clear during operation
Correct: A — Warm, moist outside air infiltrating through the door leaks, adding latent and sensible load and frosting the coil
Infiltration through a torn sweep and leaking gasket admits warm, moist air, which loads the box and frosts the coil, especially after frequent door use. A regulator fault in option B would show in suction-pressure readings, an oversized compressor in option C would short-cycle even without delivery periods, and option D describes a normal clear glass, not an air leak.
Reference: Modern Refrigeration and Air Conditioning; ASHRAE refrigeration practice
C. Ductwork
Question 19 — Air Distribution, Duct Design & Airflow
A designer finds total external static pressure available for ducts is 0.30 in. w.c. and the total effective length is 300 ft. What friction rate should be used for sizing?
- 0.03 in. per 100 ft
- 0.10 in. per 100 ft
- 0.30 in. per 100 ft
- 1.00 in. per 100 ft
Correct: B — 0.10 in. per 100 ft
Friction rate = (available static x 100) / total effective length = (0.30 x 100) / 300 = 0.10 in. per 100 ft, so B is correct. A understates the available pressure, C confuses total static with the per-100-ft rate, and D is ten times too high and would grossly undersize ducts.
Reference: ACCA Manual D
Question 20 — Air Distribution, Duct Design & Airflow
A 3-ton cooling system is designed for 400 CFM per ton in a humid climate where the designer intentionally selects 350 CFM per ton to improve latent removal. What total airflow should the blower deliver?
- 400 CFM
- 750 CFM
- 1,050 CFM
- 1,200 CFM
Correct: C — 1,050 CFM
Total airflow is 3 tons x 350 CFM per ton = 1,050 CFM, so C is correct. A is a per-ton value, not the total, B uses an incorrect multiplier, and D is the total at 400 CFM per ton rather than the selected 350 CFM per ton.
Reference: ACCA Manual D; ACCA Manual S
Question 21 — Air Distribution, Duct Design & Airflow
Which pressure in a duct system is the force that pushes air through fittings, coils, and filters and is measured with a manometer?
- Static pressure
- Velocity pressure only at the fan outlet
- Barometric pressure
- Refrigerant head pressure
Correct: A — Static pressure
Static pressure is the outward pressure in the duct that overcomes resistance from filters, coils, and fittings, so A is correct. Velocity pressure describes moving air only and does not alone describe resistance, barometric pressure is atmospheric pressure, and head pressure is a refrigeration term unrelated to duct resistance.
Reference: ACCA Manual D
D. Gas piping
Question 22 — Piping, Brazing & Gas Piping
When soft-soldering (sweating) a copper joint for HVAC water-side work, what sequence produces a sound joint?
- Clean and flux the surfaces, assemble, heat the fitting, and let capillary action draw solder into the joint
- Heat the solder rod directly with the torch until it drips and runs onto a cold, uncleaned fitting that was never fluxed or prepared
- Apply flux after the joint has cooled to seal the outside
- Melt solder into the gap with no flux on oxidized tubing
Correct: A — Clean and flux the surfaces, assemble, heat the fitting, and let capillary action draw solder into the joint
Soldering depends on clean, fluxed surfaces and heating the fitting so capillary action pulls molten solder through the joint, option A. Heating solder over a cold dirty fitting (B) produces a weak surface blob, flux after cooling (C) cannot clean oxides or promote flow inside the joint, and omitting flux on oxidized copper (D) prevents wetting and bonding.
Reference: Modern Refrigeration and Air Conditioning
Question 23 — Piping, Brazing & Gas Piping
A technician brazes refrigerant-line joints without flowing any gas through the tubing. The inside of the finished joint is later found coated with black scale that flakes off. What practice prevents this?
- Brazing with both ends of the tubing sealed completely airtight so the oxygen already inside is trapped and heated along with the joint
- Flowing low-pressure dry nitrogen through the tubing during brazing to displace oxygen and prevent internal oxidation
- Flushing the finished lines with water to wash the scale out
- Using more flux inside the tubing to coat the scale
Correct: B — Flowing low-pressure dry nitrogen through the tubing during brazing to displace oxygen and prevent internal oxidation
A gentle nitrogen purge during brazing displaces oxygen so cupric oxide scale does not form inside the tube, option B; the flakes otherwise circulate and clog metering devices and filters. Sealing air inside (A) guarantees oxidation, water flushing (C) introduces moisture that must then be removed, and internal flux (D) contaminates the refrigerant circuit rather than preventing scale.
Reference: Modern Refrigeration and Air Conditioning
E. Venting, ventilation & combustion air
Question 24 — Ventilation, Venting, Combustion Air & IAQ
What is the basic purpose of whole-dwelling mechanical ventilation under residential ventilation guidance such as ASHRAE 62.2?
- To replace all mechanical heating and cooling with outdoor air throughout the year, in every season and in every climate, without any supplemental conditioning
- To pressurize the house so no air can ever leave
- To provide controlled outdoor air to dilute indoor pollutants and maintain acceptable indoor air quality
- To remove the need for any local kitchen or bathroom exhaust
Correct: C — To provide controlled outdoor air to dilute indoor pollutants and maintain acceptable indoor air quality
Controlled outdoor air dilutes pollutants that build up in tight homes, which is the purpose of whole-dwelling ventilation. It supplements rather than replaces heating and cooling. No practical system seals a house against all exfiltration, and local exhaust for moisture and cooking sources is still required alongside whole-dwelling air.
Reference: ASHRAE 62.2 ventilation and IAQ guidance
Question 25 — Ventilation, Venting, Combustion Air & IAQ
A bathroom without an operable window has a noisy exhaust fan that occupants never use, and mirrors and paint show chronic moisture damage. What is the best correction?
- Install a larger mirror and advise shorter showers only
- Recirculate the exhaust fan discharge into the attic space above the bathroom to save energy and avoid cutting a vent termination through the roof
- Seal the bathroom door so moisture stays in one room
- Provide effective, quiet local exhaust vented outdoors, controlled so it actually runs during and after showers
Correct: D — Provide effective, quiet local exhaust vented outdoors, controlled so it actually runs during and after showers
Moisture must be captured and discharged outdoors by exhaust occupants will tolerate and controls that ensure run time. A bigger mirror does nothing about moisture load. Venting into an attic deposits moisture in the structure, and sealing the door traps humid air against finishes.
Reference: IMC ventilation provisions
Question 26 — Ventilation, Venting, Combustion Air & IAQ
A home installs a 600 cfm kitchen range hood in a tight new house with a natural-draft water heater. What concern must be addressed?
- Makeup air is needed so the hood does not depressurize the house and backdraft combustion appliances
- The hood will over-ventilate the bedrooms with fresh air
- The water heater will produce too much combustion air on its own
- No concern exists because a ducted range hood only moves air around inside the kitchen and never removes any air from the house or changes indoor pressure
Correct: A — Makeup air is needed so the hood does not depressurize the house and backdraft combustion appliances
Large exhaust can pull the house negative and reverse flow in natural-draft flues, spilling combustion products, so makeup air is required at larger hood capacities. The risk is depressurization, not over-ventilation of bedrooms. The water heater does not supply makeup air, and a ducted hood exhausts air out of the house rather than merely moving it indoors.
Reference: IMC ventilation provisions
F. Codes, standards & applied practice
Question 27 — Controls & Electrical for HVAC
A 40 VA, 24 V control transformer supplies a system. What is the maximum secondary current it can supply continuously before it is overloaded?
- About 0.60 A, from 24 V divided by 40 VA
- About 1.67 A, from 40 VA divided by 24 V
- About 16.7 A, from 40 VA multiplied by 24 V divided by 10
- About 960 A, from 40 VA multiplied by 24 V
Correct: B — About 1.67 A, from 40 VA divided by 24 V
Current equals volt-amperes divided by voltage, so 40/24 is about 1.67 A. Dividing voltage by VA reverses the relationship and gives a meaningless low value. Multiplying VA by voltage, in either scaled form, greatly overstates a small control transformer's capacity.
Reference: NFPA 70 (NEC) HVAC provisions
Question 28 — Controls & Electrical for HVAC
How does a contactor differ most usefully from a small plug-in relay in HVAC work?
- A contactor operates only on DC voltage while a relay operates only on AC
- A contactor has no movable contacts and never wears
- A contactor is built to switch larger motor and compressor loads repeatedly
- A relay must always be used for compressors because it is sealed
Correct: C — A contactor is built to switch larger motor and compressor loads repeatedly
Contactors are rated for high-current motor loads such as compressors and their contacts and arc handling suit that duty. Both device types can be built for AC or DC coils, so voltage type is not the distinction. Contactors do have movable, wearing contacts. Sealed small relays are not the required or suitable choice for compressor loads.
Reference: Manufacturer installation and service literature for HVAC controls
Question 29 — Controls & Electrical for HVAC
What keeps a permanent split capacitor (PSC) motor running efficiently after starting?
- A run capacitor that remains in the circuit with the auxiliary winding
- A start capacitor that is removed by a centrifugal switch
- A set of brushes that shift current to the rotor
- A potential relay that drops out the start winding entirely
Correct: A — A run capacitor that remains in the circuit with the auxiliary winding
A PSC motor keeps its run capacitor and auxiliary winding energized continuously, giving running torque and efficiency. A removed start capacitor describes a capacitor-start design, not PSC operation. PSC motors have no brushes, and dropping out the auxiliary winding entirely would defeat the PSC design.
Reference: Manufacturer installation and service literature for HVAC controls
Question 30 — Safety, Testing & Code Practice
Before opening an air handler to replace a blower motor, what is the correct lockout/tagout sequence?
- Turn the thermostat off and begin work
- Open the disconnect, lock and tag it, and verify absence of voltage with a meter
- Remove the filter first, then decide
- Have a coworker hold the disconnect closed so power can be restored quickly if the motor will not start
Correct: B — Open the disconnect, lock and tag it, and verify absence of voltage with a meter
Safe service requires de-energizing at the disconnect, applying lock and tag, and verifying zero voltage before touching conductors, so B is correct. A thermostat is not a disconnect and can be overridden, C delays isolation, and D defeats the purpose of lockout entirely.
Reference: OSHA 29 CFR 1926; OSHA lockout/tagout guidance
Question 31 — Safety, Testing & Code Practice
Which PPE is appropriate when cutting sheet metal and handling refrigerant with risk of frostbite burns?
- No protection if experienced
- Cotton gloves only for all tasks
- Cut-resistant gloves and safety glasses for metal work; insulated gloves and eye protection for refrigerant
- A respirator instead of eye protection
Correct: C — Cut-resistant gloves and safety glasses for metal work; insulated gloves and eye protection for refrigerant
Task-matched PPE – cut-resistant gloves and glasses for sharp metal, insulated gloves and eye protection against liquid refrigerant – is correct, so C is chosen. Experience does not replace PPE, cotton gloves do not stop cuts or frostbite, and a respirator does not protect eyes.
Reference: OSHA 29 CFR 1926
Question 32 — Safety, Testing & Code Practice
A technician sets an extension ladder on soft, uneven ground at a steep angle and plans to carry tools in both hands. What should be corrected first?
- Place the ladder on a firm, level base at a proper angle and maintain three points of contact, using a tool belt or hoist
- Lean farther back to balance
- Remove the ladder feet
- Work faster to reduce exposure
Correct: A — Place the ladder on a firm, level base at a proper angle and maintain three points of contact, using a tool belt or hoist
Stable footing, correct angle (about 4-to-1), and three points of contact are foundational ladder safety, so A is correct. Leaning back, removing feet, and rushing all increase fall risk rather than reduce it.
Reference: OSHA 29 CFR 1926
Question 33 — Refrigerants, Recovery & Handling
Under the ASHRAE safety classification system, a refrigerant classified A2L is best described as:
- Lower toxicity, with mild flammability – low burning velocity and higher ignition energy than A2 or A3 refrigerants
- Higher toxicity and nonflammable
- Lower toxicity and highly flammable like a hydrocarbon, with a very fast burning velocity, low ignition energy, and behavior similar to propane in an open flame test
- Nonflammable with no flame propagation under any test condition
Correct: A — Lower toxicity, with mild flammability – low burning velocity and higher ignition energy than A2 or A3 refrigerants
Class A means lower toxicity and the 2L subclass means the refrigerant is mildly flammable with a slow burning velocity, as with R-32 and R-454B. Option B describes a B-class toxicity rating, option C describes A3 refrigerants such as propane, and option D describes class 1 refrigerants with no flame propagation.
Reference: ASHRAE Standard 15 and Standard 34; Modern Refrigeration and Air Conditioning
Question 34 — Refrigerants, Recovery & Handling
Refrigerant that has been reclaimed differs from refrigerant that has merely been recovered or recycled because reclaimed refrigerant:
- Is simply removed from a system and stored in a recovery cylinder
- Is cleaned on site, typically with filtration and oil separation, for reuse only in the same owner's equipment, without any laboratory analysis or verification that it meets virgin-product purity specifications for general resale
- Has been reprocessed off site and verified by chemical analysis to meet virgin-product purity specifications, so it can be used in any owner's equipment
- Is destroyed by high-temperature incineration
Correct: C — Has been reprocessed off site and verified by chemical analysis to meet virgin-product purity specifications, so it can be used in any owner's equipment
Reclaim means reprocessing to virgin purity specifications with verified analysis, which is a higher standard than recovery or on-site recycling. Option A is the definition of recovery, option B is the definition of recycling, and option D describes destruction, not reclaim.
Reference: EPA 40 CFR 82 Subpart F; Modern Refrigeration and Air Conditioning
Question 35 — Plan Reading & Construction Documents
On a mechanical floor plan, a rectangular duct run is drawn with two parallel lines and a center dimension. What does the double-line drawing primarily show?
- The route the installer should follow for refrigerant piping that must be run inside the duct for freeze protection during winter operation
- The duct drawn to scale in its actual width
- A demolition boundary indicating existing ductwork that the crew must remove before any new sheet metal is fabricated for the project
- The path reserved for future ductwork that is not part of the current contract and should be left completely empty during rough-in
Correct: B — The duct drawn to scale in its actual width
Double-line duct is drawn to scale so its actual size and clearances can be checked against the space. It does not locate refrigerant piping inside the duct, mark demolition limits, or reserve a path for future work outside the contract.
Reference: Construction drawing and specification practice; SMACNA duct construction guidance
G. Embedded law layer (PA 407 + PA 230)
Question 36 — Michigan Licensing Law & Rules
Under Michigan law, mechanical contractors are regulated under which part of the state's skilled trades statute?
- Article 8 of the Skilled Trades Regulation Act, 2016 PA 407
- Article 7 of the Skilled Trades Regulation Act, 2016 PA 407
- Article 11 of the Skilled Trades Regulation Act, 2016 PA 407
- A standalone mechanical contractors act administered apart from the skilled trades statute
Correct: A — Article 8 of the Skilled Trades Regulation Act, 2016 PA 407
Mechanical contractors are regulated under Article 8 of the Skilled Trades Regulation Act, 2016 PA 407. Articles 7 and 11 of that act cover other trades, not mechanical contractors.
Reference: mi-facts fact 1; MCL 339.5801-339.5819
Question 37 — Michigan Licensing Law & Rules
Which set lists work classifications for which a Michigan mechanical contractor's license is issued?
- Electrical contracting, plumbing, and building contracting are among the ten classifications
- Elevator installation, boiler inspection, and fire alarm work are among the ten classifications
- General contracting, residential building, and maintenance and alteration work are among the ten classifications, together with the limited and unlimited service classifications issued under the administrative rules
- Hydronic heating and cooling and process piping, HVAC equipment, ductwork, and refrigeration are among the ten classifications
Correct: D — Hydronic heating and cooling and process piping, HVAC equipment, ductwork, and refrigeration are among the ten classifications
The ten classifications include hydronic heating and cooling and process piping, HVAC equipment, ductwork, and refrigeration, along with the limited and unlimited service classifications, fire suppression, and specialty. The other sets name licenses from different regulatory schemes.
Reference: mi-facts fact 3; MCL 339.5807(2)
Question 38 — Michigan Licensing Law & Rules
An applicant wants licenses in two different mechanical work classifications. What does Michigan require?
- A single examination covering all classifications the applicant selected on one application form
- One examination, with the second classification added automatically after a year of licensed work, supported by a short written attestation of experience in each one
- A separate examination only when the two classifications are in different service categories
- A separate examination for each classification sought, with the required experience in each classification applied for
Correct: D — A separate examination for each classification sought, with the required experience in each classification applied for
A separate examination is required for each classification sought, and experience is required in each work classification the applicant applies for. One examination never covers two classifications.
Reference: mi-facts facts 3, 18; MCL 339.5807(1)
Question 39 — Trade Application
A technician measures a suction-line temperature of 52°F at the evaporator outlet. The evaporating saturation temperature is 42°F. What is the evaporator superheat?
- The evaporator superheat is 10°F, found by subtracting 42°F from 52°F
- The evaporator superheat is 94°F, found by adding the two temperatures together
- The evaporator superheat is 5°F, found by dividing the temperature difference in half
- The evaporator superheat is 42°F, equal to the evaporating saturation temperature alone
Correct: A — The evaporator superheat is 10°F, found by subtracting 42°F from 52°F
Superheat is the suction-line temperature minus the evaporating saturation temperature, so 52°F minus 42°F equals 10°F. Adding the temperatures or using the saturation temperature alone does not measure superheat.
Reference: mi-facts fact 39; superheat measurement principles (edition-stable)
Question 40 — Trade Application
A liquid line measures 95°F and the condensing saturation temperature is 110°F. What is the condenser subcooling?
- The condenser subcooling is 55°F, found by dividing 110°F by the liquid-line reading
- The condenser subcooling is 205°F, found by adding the two temperatures together
- The condenser subcooling is 15°F, found by subtracting 95°F from 110°F
- The condenser subcooling is 95°F, equal to the liquid-line temperature alone
Correct: C — The condenser subcooling is 15°F, found by subtracting 95°F from 110°F
Subcooling is the condensing saturation temperature minus the liquid-line temperature, so 110°F minus 95°F equals 15°F. The other results come from adding, dividing, or copying a single reading.
Reference: mi-facts fact 39; subcooling measurement principles (edition-stable)
Question 41 — Trade Application
A cooling system shows very low superheat at the evaporator outlet on repeated readings. What is the most direct operating concern?
- The main concern is that the evaporator coil will run dry and lose all heat transfer
- The main concern is that the condenser will reject too much heat on mild days
- The main concern is that the metering device will stop opening altogether
- The main concern is liquid refrigerant flooding back toward the compressor
Correct: D — The main concern is liquid refrigerant flooding back toward the compressor
Very low superheat means little margin before liquid leaves the evaporator, so liquid can flood back toward the compressor and damage it. A dry, starved evaporator is associated with high superheat instead.
Reference: mi-facts fact 39; superheat diagnosis principles (edition-stable)
Question 42 — Business & Law Practice
A complete bid for a rooftop unit replacement should include which set of cost elements?
- Direct labor, materials, equipment, permits, overhead, and profit
- Only the purchase price of the rooftop unit and the sales tax charged on that equipment purchase
- Direct labor and materials only, because overhead and profit are handled separately after the job is awarded
- Materials, advertising expense for the season, and office rent, with field labor treated as an owner draw
Correct: A — Direct labor, materials, equipment, permits, overhead, and profit
A is correct because a complete bid recovers direct job costs plus permits, overhead, and profit. B is incorrect because it omits labor, overhead, and profit needed to perform the work. C is incorrect because excluding overhead and profit from the bid understates the selling price. D is incorrect because it mixes period marketing costs into job cost while misclassifying field labor.
Reference: NASCLA Contractors Guide to Business, Law and Project Management (general concepts); General contractor estimating and job-costing practice (industry standard concepts)
Back to the program: Michigan HVAC Exam Prep · Michigan HVAC Exam Guide · the free 20-question sample.
Disclaimer
PassProfessor is an independent exam-preparation provider. This program is exam preparation only: it is not the real exam, it provides no education credit, and completing it does not by itself qualify you for any license or certification. The real exam is run by its own exam body — you register for it, pay its fees, and sit it through that body, not through PassProfessor. All practice questions in this program are written by PassProfessor; they are not actual exam questions.