Worked practice questions for the HVACR Trade portion of the New Jersey Master HVACR Contractor licensure examination, administered by PSI Services LLC. The Trade portion presents 50 questions in 130 minutes, open book, across PSI’s published 8-area outline, and it is passed independently of the Business and Law portion. The passing standard is published in two forms: the Board’s rule, N.J.A.C. 13:32A-2.3(d), states that an applicant must receive “a minimum grade of 70 in each of the two areas,” and PSI’s bulletin states the standard for this portion as 70% (35 correct). Every worked answer below is explained and keyed to this portion’s reference layer: the International Mechanical Code, 2021, the International Fuel Gas Code, 2021, and ACCA Manual J (2016 reprint), with the bulletins’ Trade study sources cited as study sources only.
Against this portion’s limit of 15 worked questions (30 percent of the 50 presented), 13 are published here and 2 are held in reserve. The free 20-question sample is separate and does not count toward this limit. Business and Law worked questions are published separately, against that portion’s own limit: New Jersey HVAC Business and Law Practice Questions. The program page is New Jersey HVAC Exam Prep, and the free sample — free, with no enrollment required — is at the New Jersey HVAC free sample.
Worked questions for the HVACR Trade portion
Heating and Cooling Principles, Theory, and Equipment
A 3-ton R-410A split A/C cools poorly on a 92°F day. Readings: suction 98 psig, head 282 psig, suction superheat 24°F, liquid subcooling 3°F, compressor amps 78% of rated, evaporator coil clean, airflow verified at 400 cfm/ton, and no temperature drop across the liquid-line drier. What is the most likely cause?
- A. Noncondensables trapped in the condenser after a poor evacuation, which would drive head pressure and subcooling well above normal rather than low
- B. Severely reduced evaporator airflow from a clogged filter or coil, which would pull superheat down toward 2–5°F instead of leaving it at 24°F
- C. A restricted liquid-line filter drier, which would show a measurable temperature drop and often frost at the drier outlet while subcooling stayed high
- D. Low refrigerant charge
Correct: D
Low suction and head pressures together with high superheat and very low subcooling is the classic undercharge pattern: the evaporator is starved and little liquid backs up in the condenser. A drier restriction is ruled out by the absence of a temperature drop across it and by the low subcooling, low airflow would lower superheat rather than raise it, and noncondensables would raise head pressure and subcooling, the opposite of these readings.
On a 95°F day a system shows very high head pressure, high discharge-line temperature, slightly high subcooling, and near-normal superheat. The condenser coil is visibly matted with dirt and cottonwood. What is the correct first corrective action?
- A. Recover refrigerant until the head pressure looks normal, then recheck superheat
- B. Add refrigerant, because high head pressure means the condenser needs more liquid seal
- C. Clean the condenser coil and verify condenser fan operation, then recheck the readings
- D. Replace the TXV, because high head pressure proves the valve is stuck closed
Correct: C
A fouled condenser cannot reject heat, so condensing pressure and discharge temperature climb; restoring heat rejection is the first fix before any charge judgment is made. Option A would leave the system undercharged once the coil is clean, masking the real fault. Option B adds to an already excessive pressure problem, and option D is unsupported because the near-normal superheat shows the metering device is still controlling.
Refrigerants and Refrigeration
In a standard vapor-compression system, in what order does refrigerant pass through the four major components, starting at the compressor outlet?
- A. Compressor to condenser to metering device to evaporator, then back to the compressor
- B. Compressor to metering device to condenser to evaporator, then back to the compressor
- C. Compressor to evaporator to condenser to metering device, then back to the compressor
- D. Compressor to condenser to evaporator to metering device, then back to the compressor
Correct: A
Refrigerant leaves the compressor as high-pressure vapor, rejects heat and condenses, is throttled at the metering device, then absorbs heat in the evaporator before returning to the compressor. Option B throttles hot discharge gas before it can condense, option C puts the evaporator before the condenser, and option D places the metering device after the evaporator, so none of those can sustain the cycle.
A walk-in cooler compressor has a hot discharge line, high head pressure, and normal suction pressure shortly after a condenser fan belt was replaced. Inspection shows the new fan is rotating the wrong way. Why does reversed condenser airflow raise head pressure?
- A. It pushes refrigerant backwards through the compressor, reversing the entire vapor-compression cycle and forcing discharge gas back into the suction line
- B. It supercools the liquid line excessively
- C. It reverses flow through the metering device
- D. It reduces air volume through the condenser, so heat rejection falls and condensing pressure must rise to reject the same heat
Correct: D
With less air through the coil, the condenser can only reject the required heat at a higher condensing temperature and pressure. Option A is impossible because fan direction does not reverse refrigerant flow, option B would lower rather than raise pressure, and option C confuses air flow with refrigerant flow through the metering device.
Electrical Knowledge, Motors, and Controls
Intermittent no-cool and no-heat complaints. The 40 VA control transformer reads 26.4 V unloaded, but secondary voltage sags to 19.2 V whenever the contactor, gas valve, and an added humidifier solenoid energize together. Estimated combined control load is about 58 VA. The contactor buzzes and sometimes fails to pull in. What is the most likely cause?
- A. A thermostat with a failing battery that resets the display under load, which would interrupt the call signal itself rather than leave calls present while secondary voltage sags to 19.2 V
- B. A shorted contactor coil drawing the transformer down, ruled out because the coil ohms out in its normal range and the sag appears only when several control loads run together
- C. An overloaded control transformer
- D. High line voltage overheating the transformer primary, which would raise unloaded secondary voltage well above 26.4 V and cause failures even with no control loads energized
Correct: C
Unloaded voltage is healthy at 26.4 V, but roughly 58 VA of combined load on a 40 VA transformer pulls the secondary down to 19.2 V, too low for reliable contactor pull-in. A thermostat battery fault would interrupt the call rather than sag voltage with calls present, a shorted coil would ohm out abnormally and sag the circuit by itself, and high line voltage would elevate the unloaded reading and cause trouble at no load as well.
Intermittent no-cool. The system cools well for about an hour, then the outdoor unit stops for roughly 20 minutes and restarts on its own, repeating through hot afternoons. During a dropout, the contactor coil has a full 24 V at its terminals yet is not pulled in, indoor blower and thermostat call continue normally, and compressor pressures are equalizing normally (not a pressure trip). Pulled after a dropout, the coil measures open circuit while hot but returns to about 16 ohms after cooling on the bench. What is the most likely cause?
- A. A thermostat with an anti-short-cycle delay that lengthens in heat, which would remove the 24 V call during its delay rather than leave full voltage sitting at a coil that will not pull in
- B. A high-pressure switch tripping on hot afternoons, which would open the control circuit and remove coil voltage instead of leaving 24 V present at the terminals during the dropout
- C. A compressor internal overload cycling the unit, which would stop the compressor only while the condenser fan kept running and the contactor stayed pulled in
- D. A contactor coil that opens thermally when hot and recovers as it cools
Correct: D
Voltage is present but the coil will not pull in, and the coil itself proves open while hot and normal at 16 ohms when cool, a classic thermal intermittent that matches the run-an-hour, rest-20-minutes rhythm. A thermostat delay or pressure switch would remove coil voltage during the dropout, and a compressor overload leaves the contactor pulled in with the fan still running.
Piping — Refrigeration, Hydronic, Steam, Process
While brazing refrigerant piping, a low flow of dry nitrogen is passed through the tubing primarily to:
- A. Cool the joint so the filler metal does not melt
- B. Prevent black cupric oxide scale from forming inside the pipe, which could later clog driers, screens, and valves
- C. Pressurize the system to its test pressure during brazing
- D. Purge refrigerant out of the compressor windings
Correct: B
Nitrogen displaces oxygen inside the tube during heating, so internal oxide scale does not form and later flake into the system. Option A is opposite to brazing, which requires melting filler metal, option C confuses a gentle purge with a later regulated pressure test, and option D describes no real function of a piping purge.
A steam radiator bangs loudly (water hammer) and stays only partly warm, the radiator's steam trap outlet pipe is as hot as its inlet (live steam blowing through on a temperature test), returns are overheating, and other radiators on the same main now heat unevenly since the banging began. What is the most likely cause?
- A. An undersized radiator vent, which slows air release and heating of that radiator but cannot put live steam into the return line
- B. A pitched radiator trapping condensate because it slopes away from the valve, which causes hammer in that radiator but not live steam measured in the return
- C. A boiler foaming from dirty water, which typically causes surging water levels and wet steam system-wide rather than one trap passing live steam
- D. A steam trap failed open
Correct: D
Equal inlet and outlet trap temperatures prove the trap passes live steam into the return, pressurizing it, disturbing other radiators, and causing hammer. A pitch problem keeps steam out rather than blowing it through, foaming is a system-wide water condition, and a vent cannot admit steam to the return.
Fuel and LP Gas
A natural gas furnace is being converted to propane with the correct kit. Why are the propane burner orifices smaller than the natural gas orifices they replace?
- A. Smaller orifices compensate for propane being a weaker fuel per cubic foot, by forcing the gas valve to stay open longer on each heating cycle than it did on natural gas
- B. Propane is richer per cubic foot and is supplied at higher manifold pressure
- C. Smaller orifices are used only to slow the gas meter, because propane is billed by orifice size rather than by the volume or weight of fuel actually delivered
- D. Propane orifices are smaller because propane burners must run at a much lower input than the nameplate rating, typically about half the natural gas input for the same furnace
Correct: B
Propane carries more heat per cubic foot and is burned at a higher manifold pressure, so a smaller opening passes the volume needed for the rated input. Using the larger natural gas opening would overfire the furnace, and the goal is the same nameplate input, not a longer cycle, a slower meter, or half rating.
Manifold pressure is set with a manometer teed into the gas valve outlet tap. The burners must be:
- A. Firing, with the appliance calling for heat
- B. Off, because manifold pressure is a static reading that is taken with the regulator holding pressure against closed burner orifices only
- C. In pre-purge with the inducer running, because the inducer draft is what determines the pressure reading at the outlet pressure tap
- D. Lit only on the pilot or first stage of any appliance, because full firing changes the reading and is not how the setting is verified
Correct: A
Firing, with the appliance calling for heat. A static off reading, a pre-purge reading, and pilot-only firing do not show the regulated pressure the burners actually receive at operating input.
Combustion Air, Chimneys, Flues and Vents
After a hood is installed, gas water heaters in the same building begin spilling flue gas at their draft hoods whenever the kitchen is in full operation. What connects the two events?
- A. The hood's grease filters are loaded, which changes the gas pressure in the water heaters' supply piping during operation
- B. The exhaust system is depressurizing the building because makeup air is insufficient, and the negative pressure pulls flue gas back down the vents
- C. The water heaters are oversized, and an oversized heater always spills flue gas regardless of the pressure around it
- D. The kitchen exhaust fan is wired to the same circuit as the heaters, so the fan is stealing combustion air through the wiring, so the proper remedy is to move the exhaust fan onto a separate electrical panel fed from a different transformer
Correct: B
A starved exhaust system makes the building a vacuum that competes with natural-draft vents, causing backdrafting and spillage. Option A invents a path between dirty filters and gas piping pressure, option C blames sizing for a pressure-driven failure, and option D confuses an electrical coincidence with an air-balance mechanism.
Ducts, Ventilation and Exhaust
One bedroom is always warm in cooling while the rest of the house is comfortable. Its register delivers about 18 CFM against a design of roughly 95 CFM; all other registers measure near design, system static pressure is normal, and the branch damper is verified open. In the attic, that bedroom's flex duct makes a sharp bend at a truss and is visibly crushed where it crosses it. What is the most likely cause?
- A. The kinked and crushed flex branch duct serving that room
- B. A system-wide airflow shortage from the blower, which would depress airflow at every register in the house rather than leave all but one branch at its design flow
- C. A closed zone damper starving one side of the house, ruled out because the branch damper is verified open and neighboring branches on the same trunk measure normally
- D. An undersized supply trunk for the whole system, which would show elevated static pressure and broadly weak registers instead of one crushed branch at normal static
Correct: A
Only the one branch is starved, total static is normal, and the physical inspection finds that branch kinked and crushed at a truss, throttling its roughly 95 CFM design flow down to 18 CFM. A blower or trunk problem would depress many registers and change static pressure, and the branch damper is proven open.
Load Calculations
A load calculation shows 28,500 Btuh total cooling with 21,000 Btuh sensible. When selecting equipment per Manual S, the technician should:
- A. Choose equipment whose total and sensible capacities at design conditions match the loads without gross oversizing
- B. Always choose the largest unit available
- C. Match only the nameplate tonnage to the square footage
- D. Ignore sensible capacity if total capacity matches
Correct: A
Manual S requires matching both total and sensible capacity at actual design conditions to the calculated loads, avoiding gross oversizing, so A is correct. B invites short-cycling, C uses a rule of thumb instead of a load calc, and D risks failing to meet the sensible load or control humidity.
Disclaimer
PassProfessor is an independent exam-preparation provider. This program is exam preparation only: it is not the real exam, it provides no education credit, and completing it does not by itself qualify you for any license or certification. The real exam is run by its own exam body — you register for it, pay its fees, and sit it through that body, not through PassProfessor. All practice questions in this program are written by PassProfessor; they are not actual exam questions.