New Jersey HVAC Sample Practice Questions

New Jersey HVAC Sample Practice Questions

The free sample for PassProfessor’s New Jersey HVAC Exam Prep, republished here exactly as served in the program’s free sample exam: 20 questions, in serve order, each with its answer and explanation. The sample is free and requires no enrollment. As served, it draws on 14 of the bank’s 19 topic areas; the full program’s drills cover all 19. To take the sample as a scored quiz, use the free sample exam. The program page is New Jersey HVAC Exam Prep and the companion guide is the New Jersey HVAC Exam Guide.

The 20 free sample questions, as served

Why are tandem (paired) compressors used instead of one large compressor on some packaged units?

  • A. Because two compressors piped together always use exactly half the energy of one compressor of the same total capacity at every possible operating condition
  • B. Because a tandem pair eliminates the need for any oil equalization or shared oil management between the two crankcases under all load combinations
  • C. Because a single compressor cannot be manufactured above a very small size, so any unit over a few tons must always use two compressors in tandem
  • D. Staged capacity and redundancy, with each compressor sized for part of the total load

Correct: D

Tandem pairs stage capacity to match part load and keep partial cooling if one machine fails. They do not halve energy use at every condition, their shared piping still requires careful oil equalization, and large single compressors are readily available, so pairing is a staging choice, not a size limit.

After a severe hermetic compressor burnout, the replacement plan that best protects the new compressor is:

  • A. Change only the compressor and reuse all driers unchanged
  • B. Flush the system with liquid refrigerant from a charging cylinder, pushing the full cylinder contents through the suction and liquid lines, out through the evaporator, and venting the contaminated mixture at the far end of the run before installing the new compressor
  • C. Test the oil/refrigerant for acid, install new liquid-line and suction cleanup driers/filters sized for cleanup, run, retest, and replace cleanup cores/driers until tests stay clean
  • D. Add extra oil to dilute any acid so no driers are needed

Correct: C

Burnout debris and acid circulate system-wide, so cleanup driers on both lines, acid testing, and repeat checks until clean are the standard protection for the new compressor. Option A leaves contamination to kill the replacement, option B is an improper and wasteful flushing method, and option D dilutes nothing safely because acid remains active in the oil.

Where must an appliance fuel-gas shutoff valve be located?

  • A. In a different room from the appliance, behind a locked panel, so it cannot be reached while the appliance is operating at full input
  • B. At the meter set only, since individual appliance shutoffs are not permitted anywhere downstream of the meter in a building system
  • C. Inside the appliance cabinet, reachable only after the burner access panel and the blower panel have both been removed by a technician
  • D. Accessible, in the same room as the appliance, within 6 feet of the appliance it serves

Correct: D

An appliance shutoff valve must be accessible, in the same room as the appliance, and within 6 feet of the appliance it serves. That accessible same-room placement within 6 feet is the keyed requirement.

In the field, a duct main was rerouted around a new opening and now sits 4 feet from its drawn location. What must happen to the record documents?

  • A. Nothing, because field reroutes under ten feet are considered too minor to document and future crews are expected to locate concealed duct by sounding walls
  • B. The original plan should be destroyed and replaced with a verbal description given to the building engineer during the final walkthrough meeting
  • C. The change should be photographed for the crew's own files but kept off the record set so the drawings continue to match the approved permit documents exactly
  • D. The as-built set must show the duct in its actual location

Correct: D

Record drawings must reflect what was actually built, including a 4-foot reroute, so future work can find the duct. Minor-change exemptions, verbal descriptions, and private photographs all leave the official record wrong.

What is the employer's basic duty for workplace safety and protective equipment?

  • A. To post a safety policy at the office, after which each employee bears sole responsibility for recognizing and avoiding every job hazard
  • B. To require employees to buy their own protective equipment in all cases, since providing equipment is treated as a voluntary benefit
  • C. To act only after an injury occurs, since the safety duty arises from the injury report rather than from known hazards in the work
  • D. To provide a workplace free from recognized hazards and supply needed personal protective equipment and training for its use

Correct: D

The employer must provide a workplace free from recognized hazards and supply needed personal protective equipment and training for its use. That duty is proactive; it does not wait for an injury to occur.

A compressor fails with washed-out bearings and scored surfaces, and service history shows months of operation with superheat near zero at the compressor inlet. What mechanism connects that history to this failure?

  • A. High discharge temperature from chronic overheating thinned the oil
  • B. Excessive subcooling hardened the bearing surfaces over time
  • C. Low suction pressure raised the compression ratio until the bearings scored, until the suction pressure recovered on its own
  • D. Liquid refrigerant returning to the compressor diluted and washed oil off the bearing surfaces (floodback)

Correct: D

Sustained floodback sends liquid refrigerant into the crankcase, diluting the oil and stripping the lubricating film from bearings until they score and fail. Option A describes an overheating failure, but near-zero superheat means the suction gas was cold and saturated, not overheated. Option B names a condenser-side condition with no such bearing effect, and option C contradicts the history, since floodback conditions accompany ample, not low, suction-side refrigerant.

After electrical service work, a three-phase scroll compressor starts and runs loudly with no cooling, and suction pressure rises instead of falling. The first check is:

  • A. Manifold gas pressure, because a reversed scroll compressor changes the gas valve setting of the furnace sharing the same gas line in the building
  • B. The thermostat anticipator setting, because incorrect anticipation causes compressors to run backward for complete cooling cycles at a time
  • C. Phase rotation; a scroll running backward produces little compression and can be damaged
  • D. The sediment trap at the furnace, because debris in the gas line is a common cause of electrical phase reversal at a compressor motor

Correct: C

Phase rotation; a scroll running backward produces little compression and can be damaged. Gas pressure, thermostat anticipation, and a gas-line trap have nothing to do with rotation; reversed phases after service work are the prime suspect.

Why do refrigerant records for purchases, recovery, and appliance service need dates, quantities, and the identity of the parties involved?

  • A. They create an auditable trail showing refrigerant was bought, handled, recovered, and disposed of through proper channels
  • B. They are used by suppliers to set the retail price of refrigerant each season, based on the total quantities each contractor reports purchasing during the previous year
  • C. They replace the need for certified technicians to handle refrigerant
  • D. They prove a system was charged correctly without any gauge readings

Correct: A

Traceable records demonstrate compliant handling across the refrigerant's path. Pricing is a market matter unrelated to record fields, certification requirements still apply to handlers, and paperwork alone cannot prove a correct charge, which is verified by measurement.

A contractor marks up a $1,000 job cost by 20% to set the price. What is the resulting price and its gross margin?

  • A. $1,200 price; about 16.7% margin
  • B. $1,200 price and a 20.0 percent margin, because markup on cost and margin on price are always identical
  • C. $1,250 price and a 20.0 percent margin, found by using the margin divisor formula instead of the stated markup
  • D. $1,020 price and a 2.0 percent margin, found by adding the markup rate as a flat dollar amount

Correct: A

A is correct because a 20 percent markup gives $1,200, and the $200 profit divided by $1,200 is about 16.7 percent margin. B is incorrect because a 20 percent markup does not produce a 20 percent margin. C is incorrect because it prices with the margin formula when the problem states a markup. D is incorrect because it treats 20 percent as $20 rather than 20 percent of $1,000.

A contractor operates as a sole proprietor. What is the owner's liability position for the business?

  • A. The owner is liable only up to the value of the equipment the business owns, and personal assets are protected by the business registration alone
  • B. The owner shares liability equally with every employee, so no single person is responsible for the whole of a business debt or obligation
  • C. The owner is personally liable for the debts and obligations of the business
  • D. The owner has no liability for business debts once the business obtains its own tax identification number and a separate business bank account

Correct: C

In a sole proprietorship there is no legal separation between owner and business, so the owner is personally liable for the debts and obligations of the business. That unlimited personal liability is the form's defining risk.

Why do contracting businesses retain job, payroll, and tax records for a set period after a project ends?

  • A. So the supplier can reuse the customer's equipment selections as a template for quoting unrelated future customers
  • B. To support audits, warranty questions, tax filings, and dispute resolution
  • C. Only to fill archive space required by the office lease, with no business or legal purpose served by keeping them
  • D. To allow employees to revise their recorded hours after final pay whenever they disagree with the original timesheets

Correct: B

B is correct because retained records substantiate taxes, payroll, warranty history, and the facts if a dispute or audit arises. A is incorrect because a customer's project records are not a supplier quoting template. C is incorrect because retention serves compliance and business purposes, not lease space requirements. D is incorrect because records are kept to preserve an accurate history, not to permit after-the-fact timesheet changes.

A typical contractor workmanship warranty differs from a manufacturer's equipment warranty in which way?

  • A. The workmanship warranty covers the contractor's installation work; the manufacturer's covers its equipment defects
  • B. The workmanship warranty covers the factory's equipment defects, while the manufacturer covers the contractor's labor errors
  • C. Both warranties are identical in coverage, and the distinction exists only for marketing purposes in the proposal
  • D. The manufacturer's warranty covers the contractor's installation workmanship for as long as the building remains standing

Correct: A

A is correct because the contractor warrants its own installation work while the manufacturer warrants defects in its equipment. B is incorrect because it reverses the two parties' responsibilities. C is incorrect because the coverage, responsible party, and claim route genuinely differ. D is incorrect because a manufacturer does not warrant the installing contractor's workmanship.

A condensing furnace develops intermittent pressure-switch trips in mid-winter that clear when the technician drains a large amount of water from the secondary heat exchanger area. The root cause is:

  • A. An oversized vent termination screen that gradually collects frost and lint outdoors until it blocks the entire vent outlet and shuts the furnace down on every call for heat
  • B. A high-fire manifold pressure set too low
  • C. A flame sensor coated with silica
  • D. A partially blocked condensate drain or trap that lets condensate back up into the secondary exchanger and venting path, restricting draft

Correct: D

Backed-up condensate occupies exchanger and vent passages, so draft falls intermittently until the water is drained — the drain or trap restriction is the fault to clear. Option A can restrict the vent but would not explain water draining from the exchanger. Option B affects heat output, not draft proving. Option C causes flame-proving shutdowns after ignition, not pressure-switch trips before it.

An ERV serving a northern building loses capacity and shows rising pressure drop across the core every cold snap, recovering each thaw. What is happening and what is the standard remedy?

  • A. The wheel motor is failing only in cold weather, and replacing the motor each winter is the accepted maintenance practice
  • B. Frost is building up in the core as moist exhaust air freezes — use a designed frost-control strategy such as preheat, bypass, or defrost cycle
  • C. The outdoor-air filters are loading with snow dust, which is cured by removing the filters for the entire heating season
  • D. The building is over-ventilated, and permanently closing the outdoor-air intake each winter is the standard operating remedy, and post a laminated sign instructing the operators to keep the outdoor-air intake closed until the spring thaw arrives

Correct: B

Exhaust moisture condenses and freezes in the core at low outdoor temperatures; engineered defrost or preheat keeps the unit running. Option A misdiagnoses a thermal problem as a recurring motor failure, option C sacrifices filtration for the season and still leaves frost forming, and option D abandons required ventilation instead of controlling frost.

After passing, what general liability insurance certificate must be submitted by an applicant who will offer services to the public?

  • A. A certificate for $3,000 in combined coverage, matching the surety bond amount, from any insurer the applicant chooses in any state
  • B. A certificate for $160,000 in combined coverage, matching the biennial renewal fee multiplied across the licensing period, from a NJ insurer
  • C. A certificate for $500,000 for combined property damage and bodily injury in any one accident or occurrence, from an insurer authorized in New Jersey
  • D. No certificate at all, since general liability coverage is optional for a master who acts as a bona fide representative of a licensed entity

Correct: C

The certificate must show $500,000 for combined property damage and bodily injury to or death of one or more persons in any one accident or occurrence. The insurer must be authorized and licensed to do business in New Jersey, or DOBI-approved proof of self-insurance may be submitted.

After a fuel change to propane, a furnace soots, rolls flame out of the heat exchanger openings, and trips its rollout switch. The gas valve was converted, but the original natural gas orifices are still installed. What best explains the symptoms?

  • A. The furnace is underfired because propane orifices were required to be larger, so the weak flame is being pulled out of the openings by excessive induced draft at the vent connector
  • B. The rollout trips are an electrical coincidence, because orifice size has no effect on input, flame shape, or heat exchanger temperature once the gas valve regulator is converted
  • C. Sooting after conversion is expected break-in behavior for propane, and the correct response is to reset the rollout switch repeatedly until the soot burns off the heat exchanger
  • D. The oversized natural gas orifices overfire the burners on propane

Correct: D

Natural gas orifices are too large for richer propane at propane manifold pressure, so the burners are heavily overfired, producing soot, distorted flame, and rollout. The fault is excessive rather than weak input, orifice size directly sets firing rate, and repeated rollout resets ignore a hazardous firing condition.

An HVACR contractor licensed in another state wants a New Jersey license without taking the examination. When is that possible?

  • A. The license is available without examination only if the other state's standards are equal or comparable to New Jersey's and that state permits New Jersey licensees to obtain licensure there based on a New Jersey license
  • B. The license is available without examination whenever the other state's standards are equal or comparable, even if that state does not license New Jersey licensees in return, and the applicant need not show any proof that the other state would license a New Jersey master on the same terms
  • C. The license is available without examination whenever the other state licenses New Jersey licensees in return, even if that state's standards fall below New Jersey's
  • D. The license is never available without examination, and every out-of-state applicant must pass both portions regardless of the other state's standards or treatment

Correct: A

Reciprocity requires both prongs: standards equal or comparable to New Jersey's, and the other state permitting New Jersey licensees to obtain licensure there based on a New Jersey license. The applicant submits the Board form with a full street name and number, proof of age 21, a passport-size photo taken within the last six months, proof of the education requirements, proof of the other state's reciprocal treatment and of licensure, and the application fee, and after the Board determines comparability the applicant submits the bond, insurance, and licensing fee.

Airflow complaint. With bedroom doors open the system heats and cools evenly, but with doors closed the bedrooms go stuffy, airflow at their registers drops noticeably, and a whistle sounds under the doors. There is no ducted return in the bedrooms. A manometer reads each closed bedroom about +4 Pa relative to the hallway, and the hallway side goes slightly negative. Door undercuts measure only about half an inch. What is the most likely cause?

  • A. Supply dampers to the bedrooms closing on their own, which would cut register airflow whether the doors were open or closed rather than track door position exactly
  • B. A return duct leak in the hallway zone, which would depressurize the main body regardless of bedroom door position and would not pressurize each closed bedroom in turn
  • C. A blower that slows when back pressure rises on its control board, which would reduce airflow to the whole house rather than redistribute it based on which doors are shut
  • D. Closed bedrooms pressurizing because they have no return-air path

Correct: D

Supply air enters each closed bedroom with no way back except a half-inch undercut, so the room pressurizes to about +4 Pa, supply flow into it falls, and air whistles under the door. Dampers would not track door position, a return leak would not pressurize individual rooms, and a blower response would change total airflow rather than create room-by-room pressure differences.

A new draw-through air handler on a cooling coil pulls air across the coil, so its drain pan is under negative pressure. It is piped with a straight pipe from the pan to the drain with no trap, and at startup air is sucked up the drain line and condensate overflows the pan. What was missed?

  • A. The drain needed a larger diameter so air could enter faster
  • B. A trap of adequate depth is needed so its water seal resists the negative pressure and lets condensate drain instead of being held in the pan
  • C. The pan needed a safety switch instead of any trap
  • D. The drain should have been connected to the liquid line to equalize pressure, tying the condensate piping directly into the sealed refrigerant circuit so the two pressures balance each other at startup

Correct: B

On a draw-through unit the fan can draw air up an untrapped drain and hold water in the pan until it overflows; a trap with enough depth holds a seal against that pressure difference. Option A would admit more air, option C adds protection against overflow but does not make the drain work, and option D would join condensate piping to refrigerant piping, which is never correct.

A replacement job involves connecting wiring for a 20-ton unit on a 240-volt system from an adequately sized equipment service disconnect. Which conditions must all be met for this replacement-wiring scope?

  • A. The work may be new installation wiring, the equipment may exceed 25 tons, and the voltage may exceed 240 volts if the disconnect is new
  • B. The work must be performed by an apprentice alone, the disconnect may be replaced as part of the job, and no code provision needs to be followed
  • C. The case must be a replacement, each piece of equipment must be 25 tons or less, the voltage must be 240 volts or less, and the connection must follow the Uniform Construction Code
  • D. The case must be a replacement, and no tonnage limit, voltage limit, or code requirement applies to wiring run from a service disconnect box

Correct: C

Replacement wiring is allowed in replacement cases only, from an equipment service disconnect box of adequate size. Each piece of equipment must be 25 tons or less, the system voltage must be 240 volts or less, and the connection must be performed according to all relevant Uniform Construction Code provisions; the 20-ton, 240-volt facts fit those limits.

Disclaimer

PassProfessor is an independent exam-preparation provider. This program is exam preparation only: it is not the real exam, it provides no education credit, and completing it does not by itself qualify you for any license or certification. The real exam is run by its own exam body — you register for it, pay its fees, and sit it through that body, not through PassProfessor. All practice questions in this program are written by PassProfessor; they are not actual exam questions.